Timing chart (logic 11c) – IDEC FS1A Controller User Manual
Page 100

LOGIC
5-52
Timing chart (Logic 11C)
Example: Manual start input (X16) is used. Example: Control start input (X17) is used.
Safety output 2: Y2,
Y3
Monitor output for
Safety output 2: Y13
Safety output 2: Y2,
Y3
Monitor output for
Safety output 2: Y13
Safety output 1: Y0,
Y1
Monitor output for
Safety output 1: Y12
Safety output 1:
Y0, Y1
Monitor output for
Safety output 1: Y12
Max. 0.1s
Max. 0.1s
Safety input 1: X0
Start input 1: X16
(Manual)
Monitor output for
safety input 1: Y4
State monitor output 3:
Y16
Solenoid output 2:
Y20
OFF delay time
Safety input 1: X1
Safety input 1: X0
Start input 2: X17
(Control)
Monitor output for
safety input 1: Y4
State monitor output 3:
Y16
Solenoid output 2:
Y20
Safety input 1: X1
0.1s to 5s
Max. 6s
Initialization
Max. 6s
Initialization
note 1)
note 1)
note 1)
Min. 0.1s
note 1)
Solenoid output 1:
Y17
Solenoid output 1:
Y17
Power
ON
Safety
output
ON
Power
ON
Safety
output
ON
OFF delay time
(Safety input 2 to 6 are all ON in this chart.) (Safety input 2 to 6 are all ON in this chart.)
Note 1) Input monitor error detection time is 0.1s.
About safety inputs that are not described in this chart, input monitor error detection time is as follows.
The time of dual channel safety input (X2, X3) is 0.1s.
The time of dual channel direct opening input (X4 to X13) is 0.5s.
Refer to the following “Logic functions” for more details.