ProSoft Technology MVI56-104S User Manual
Page 98

MVI56-104S ♦ ControlLogix Platform
Reference
IEC 60870-5-104 Server Communication Module
User Manual
Page 98 of 188
ProSoft Technology, Inc.
November 18, 2009
5.1.3 Hardware
Specifications
Specification Description
Backplane Current Load
800 mA @ 5 V DC
800 mA @ 24VDC
Operating Temperature
0 to 60°C (32 to 140°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Shock 30g
Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity
5% to 95% (non-condensing)
LED Indicators
Module Status
Backplane Transfer Status
Application Status
Serial Activity
Application port (Ethernet)
Ethernet Port (Ethernet modules)
10/100 Base-T
RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s,
applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal
to 5000 [ARP] frames-per-second and less than or equal to
5 minutes duration
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking