ProSoft Technology MVI56-104S User Manual

Page 149

background image

Reference MVI56-104S

♦ ControlLogix Platform

User Manual

IEC 60870-5-104 Server Communication Module


ProSoft Technology, Inc.

Page 149 of 188

November 18, 2009

Type ID

Type

Description

Data Representation

5 M_ST_NA_1

(7.3.1.5)

Monitored Step-point Information: This
data type is used for step position of

transformers or other step position

information. The value for the position

ranges from -64 to information for this

type are M_ST_TA_1 (6) and 63.

Associated time-tagged event

M_ST_TB_1 (32).

Step data (7.2.6.5) is stored in a single
character value with bits 0 to 6 (-64 to +63)

representing the step position and bit 7

representing the following states:
0 = Equipment is not in transient state
1 = Equipment in transient state

9 M_ME_NA_1

(7.3.1.9)

Monitored Normalized Measured Value:

This data type is used for analog input

data. Associated time-tagged event

information for this type are M_ME_NA_1

(10) and M_ME_TD_1 (34).

Normalized values (7.2.6.6) are stored in a (16-

bit) word data area with a range of -1..+1-2-15

11

M_ME_NB_1

(7.3.1.11)

Monitored Scaled Measured Value: This

data type is used for analog input data.

Associated time-tagged event information

for this type are M_ME_TB_1 (12) and

M_ME_TE_1 (35).

Scaled values (7.2.6.7) are stored in a (16-bit)

word data area with a range of -215.. +215-1

13 M_ME_NC_1

(7.3.1.13)

Monitored Measured Value, Short

Floating-Point Number: This data type is

used for analog input data stored in

floating point format according to the

IEEE STD 754, QDS format. Associated

time-tagged event information for this

type are M_ME_TC_1 (14) and

M_ME_TE_1 (36).

Short floating-point number stored in IEEE

STD 754 format (Fraction, Exponent, Sign)

(7.2.6.8)

15

M_IT_NA_1

(7.3.1.15)

Monitored Integrated Total-point

Information: This data type stores meter

or other count data. Associated time-

tagged event information for this type are

M_IT_TA_1 (15) and M_IT_TB_1 (37).

Binary counter data (7.2.6.9) is stored in a

double-word (32-bit) value with a range of -

231..+231-1.

45

C_SC_NA_1
(7.3.2.1)

Single-point Command: This command
controls a single binary point such as a

relay.

Single bit value (7.2.6.15) with
0 = Off and
1 = On

46 C_DC_NA_1

(7.3.2.2)

Double-point Command: This command
controls a dual-point binary control device

such as a trip/close relay.

Double Command (7.2.6.16) with
0 = Not permitted
1 = Off
2 = On
3 = Not permitted

47 C_RC_NA_1

(7.3.2.3)

Regulating Step Command: This
command controls a stepping device

such as a transformer.

Regulating Step Command (7.2.6.17) with
0 = Not permitted
1 = Next step lower
2 = Next step higher
3 = Not permitted

48 C_SE_NA_1

(7.3.2.4)

Setpoint Command, Normalized Value:

This command controls an analog device.

Normalized values (7.2.6.6) are stored in a (16-

bit) word data area with a range of -1..+1-2-15

49 C_SE_NB_1

(7.3.2.5)

Setpoint Command, Scaled Value: This

command controls an analog device.

Scaled values (7.2.6.7) are stored in a (16-

bit)word data area with a range of -215 .. +215-

1

50 C_SE_NC_1

(7.3.2.6)

Setpoint Command, Short Floating-Point

Format: This command controls an

analog device accepting an IEEE STD
754 floating-point format value.

Short floating-point number stored in IEEE

STD 754 format (Fraction, Exponent, Sign)

(7.2.6.8)