MVI56-104S ♦ ControlLogix Platform

Reference

IEC 60870-5-104 Server Communication Module

User Manual


Page 122 of 188

ProSoft Technology, Inc.

November 18, 2009

C_SE_NA and C_SE_NB

The measured normalized point command uses one word with word-addressing.
For example, if you configured the following points:

The following table describes how these points would be used.

Inf. Object Address

MVI56-104S Module Database Address

400 Word

10

401 Word

12

402 Word

18

The measured normalized points use a data representation defined by the
protocol specification, where each bit represents a value as follows:

Bit 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Value S 2

-1

2

-2

2

-3

2

-4

2

-5

2

-6

2

-7

2

-8

2

-9

2

-10

2

-11

2

-12

2

-13

2

-14

2

-15

Example: a value of 4000hex is interpreted as 0.5