M_me_nc_1 104, M_it_na_1 104 – ProSoft Technology MVI56-104S User Manual
Page 45

Configuring the MVI56-104S Module
MVI56-104S ♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 45 of 188
November 18, 2009
2.12 [M_ME_NC_1
104]
This section defines the monitored short-float point database for the slave device
emulated. This information is sourced from the database and is transferred to the
remote client unit. Each point occupies 4-byte positions in the database. To
determine the IOA (Information Object Address) for each object, add the Point #
in the following section to the value of the M_ME_NC Parameter Offset
parameter set in the previous section.
This section takes the following parameters:
Point
#
DB
Address
Groups
Default
Deadband
IV DB Bit
Each point is one word and the DB Address value corresponds to the word offset
in the database.
Refer to the Group Codes (page 49) section for a listing of Group Codes.
2.13 [M_IT_NA_1
104]
This section defines the monitored integrated totals (counter) database for the
server emulated. This information is sourced from the database and is
transferred to the remote client unit. Each point occupies two words in the
database (4 bytes).
This section takes the following parameters:
Point
#:
DB
Address:
Group(s):
IV DB Bit
Each point is two words and the DB Address value corresponds to the double-
word offset in the database.