MVI56-104S ♦ ControlLogix Platform

Reference

IEC 60870-5-104 Server Communication Module

User Manual


Page 104 of 188

ProSoft Technology, Inc.

November 18, 2009

In this example, all monitor points are located between database addresses 0
and 199, and all control points are located between address 200 and 399. The
backplane settings must also be configured to correctly update these database
ranges. For more information on configuration, refer to [Backplane Configuration]
(page 28)

Common ASDU Address

At the application level, the module is identified by the Common ASDU
(Application Service Data Unit) Address. This address must match the CASDU
sent by the client unit. An ASDU is a data unit that transfers information objects
between the client and the server.

If the client sends a message to a different Common ASDU, the module ignores
the command. To configure the Common ASDU Address for the MVI56-104S
module, use the following parameter in the configuration file: