MVI56-104S ♦ ControlLogix Platform

Diagnostics and Troubleshooting

IEC 60870-5-104 Server Communication Module

User Manual


Page 94 of 188

ProSoft Technology, Inc.

November 18, 2009

Module Errors

Problem Description

Steps to take

BP ACT LED (not
present on MVI56E
modules) remains off or
blinks slowly

MVI56E modules with
scrolling LED display:

condition reads ERR

This indicates that backplane transfer operations are failing. Connect to
the module’s Configuration/Debug port to check this.

To establish backplane communications, verify the following items:

The processor is in RUN or REM RUN mode.

The backplane driver is loaded in the module.

The module is configured for read and write data block transfer.

The ladder logic handles all read and write block situations.

The module is properly configured in the processor I/O configuration and
ladder logic.

OK LED remains RED

The program has halted or a critical error has occurred. Connect to the
Configuration/Debug port to see if the module is running. If the program
has halted, turn off power to the rack, remove the card from the rack and
re-insert the card in the rack, and then restore power to the rack.