Test procedure

(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)

Test

procedure

File transfer

(Station-specific parameter, mark "X" if function is used)

File transfer in monitor direction

Transparent

file

Transmission of disturbance data of protection equipment

Transmission of sequence of events

Transmission of sequence of recorded analogue values

File transfer in control direction

Transparent

file

Background scan

(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)

Background

scan

Definition of time outs

Parameter Default Value

Remarks

Selected Value

t

0

60 seconds

Time-out of connection establishment

60 seconds

t

1

15 seconds

Time-out of send or test APDUs

t

2

10 seconds

Time-out for acknowledges in case of no data
messages (t

2

< t

1

)

t

3

20 seconds

Time-out for sending test frames in case of a
long idle time

Maximum range of values for configurable time-outs: 1 to 255 seconds, accuracy
1 second. (t1,t2,and t3 only)