ProSoft Technology MVI56-104S User Manual
Page 168

MVI56-104S ♦ ControlLogix Platform
Reference
IEC 60870-5-104 Server Communication Module
User Manual
Page 168 of 188
ProSoft Technology, Inc.
November 18, 2009
Test procedure
(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
Test
procedure
File transfer
(Station-specific parameter, mark "X" if function is used)
File transfer in monitor direction
Transparent
file
Transmission of disturbance data of protection equipment
Transmission of sequence of events
Transmission of sequence of recorded analogue values
File transfer in control direction
Transparent
file
Background scan
(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
Background
scan
Definition of time outs
Parameter Default Value
Remarks
Selected Value
t
0
60 seconds
Time-out of connection establishment
60 seconds
t
1
15 seconds
Time-out of send or test APDUs
t
2
10 seconds
Time-out for acknowledges in case of no data
messages (t
2
< t
1
)
t
3
20 seconds
Time-out for sending test frames in case of a
long idle time
Maximum range of values for configurable time-outs: 1 to 255 seconds, accuracy
1 second. (t1,t2,and t3 only)