MVI56-104S ♦ ControlLogix Platform

Reference

IEC 60870-5-104 Server Communication Module

User Manual


Page 136 of 188

ProSoft Technology, Inc.

November 18, 2009

M_ME_NC

Monitored Measured Normalized Point

Associated Parameter Point

600 2600

601 2601

602 2602

603 2603

604 2604

Controlling the Generation of Events

Some applications may require that only some points should generate events.
The application would only poll the current value for these points, although
changes in these values would have no significance. Other applications may
require that all configured points should generate events.

The MVI56-104S module offers a lot of flexibility for event control. The user may
control if events will be generated at 3 different levels:

1 General (All Points)
2 Data Type Level
3 Point Level

General (All Points)

The user may control how frequently the module will scan the database for
events using the following configuration parameter: