ProSoft Technology MVI56-104S User Manual
Page 159

Reference MVI56-104S
♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 159 of 188
November 18, 2009
5.6.2 Application
Layer
Transmission mode for application data
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4,
is used exclusively in this companion standard.
Common Address of ASDU
(System-specific parameter)
One octet
⌧ Two octets
Information object address
(System-specific parameter)
One octet
Structured
Two octets
Unstructured
⌧ Three octets
Cause of transmission
(System-specific parameter)
One octet
⌧ Two octets (with originator address)
Length of APDU
(System-specific parameter, specify the maximum length of the APDU per
system)
The Maximum length of the APDU is 253 (default). The maximum length may be
reduced by the system.
253 Maximum length of APDU per system