Reference MVI56-104S

♦ ControlLogix Platform

User Manual

IEC 60870-5-104 Server Communication Module


ProSoft Technology, Inc.

Page 159 of 188

November 18, 2009

5.6.2 Application

Layer

Transmission mode for application data

Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4,
is used exclusively in this companion standard.

Common Address of ASDU

(System-specific parameter)

One octet

⌧ Two octets

Information object address

(System-specific parameter)

One octet

Structured

Two octets

Unstructured

⌧ Three octets

Cause of transmission

(System-specific parameter)

One octet

⌧ Two octets (with originator address)

Length of APDU

(System-specific parameter, specify the maximum length of the APDU per
system)

The Maximum length of the APDU is 253 (default). The maximum length may be
reduced by the system.

253 Maximum length of APDU per system