The following table describes how these points would be used.

Inf. Object Address

MVI56-104S Module Database Address

400 Word

10

401 Word

12

402 Word

18

The monitored measured normalized points use a data representation defined by
the protocol specification. The following table describes the value for each bit.

Bit 16 15 14 13 12

11 10 9 8 7 6 5 4 3 2 1

Value S 2

-1

2

-2

2

-3

2

-4

2

-5

2

-6

2

-7

2

-8

2

-9

2

-10

2

-11

2

-12

2

-13

2

-14

2

-15

Example: a value of 4000hex is interpreted as 0.5

M_ME_NC and M_IT_NA

The monitored measured short floating point and monitored integrated total
points occupy two words with double-word addressing.

For example, if you configured the following points:

The following table describes how these points would be used.

Inf. Object Address

Module Database Address

500

Words 40 and 41

501

Words 64 and 65

502

Word 104 and 105