C_rc_na_1 104, C_se_na_1 104 – ProSoft Technology MVI56-104S User Manual
Page 47

Configuring the MVI56-104S Module
MVI56-104S ♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 47 of 188
November 18, 2009
2.16 [C_RC_NA_1
104]
This section defines the step command database for the server emulated. This
information is sourced from the remote client and is transferred to the database.
Each point occupies a byte in the database. The control value can be associated
with a monitored point as described in the previous example.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Each point is one byte and the DB Address value corresponds to the byte offset
in the database.
2.17 [C_SE_NA_1
104]
This section defines the normalized setpoint database for the server emulated.
This information is sourced from the remote client and is transferred to the
database. Each point occupies a word position in the database. You can
associate a command with a monitored normalized database value to coordinate
the command/monitor operation. You must enter the correct Monitor Point # and
Monitor DB Addr values in the table. If the Require Select parameter is not set to
zero, a select command must be received before an execute command will be
processed.
This section takes the following parameters:
Point
#
DB
Address
Monitor
Point
#
Monitor
DB
Addr
Require
Select
Each point is one word and the DB Address value corresponds to the word offset
in the database.