ProSoft Technology MVI56-104S User Manual
Page 35

Configuring the MVI56-104S Module
MVI56-104S ♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 35 of 188
November 18, 2009
2.4.11 Common Address of ASDU
0 to 65535
This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.
2.4.12 Cyclic Data Transmission
0 to 2^32
This parameter defines the number of milliseconds between cyclic updates. The
range of values for this parameter permit update times of 1 millisecond to 5
minutes. If the parameter is set to 0, cyclic data reporting will be disabled.
2.4.13 Select/Operate Timeout
0 to 2^32
This parameter sets the number of milliseconds after a select command is
received in which to wait for a valid execute command. The range of values for
this parameter permit times of 1 millisecond to 30 seconds. If the parameter is
set to 0, the feature will be disabled.
2.4.14 Use ACTTERM with Setpoint
1 or 0
This parameter determines if an ACTTERM will be sent. If the parameter is set to
1, then setpoint commands will issue an ACTTERM when the command is
complete. If the parameter is set to 0, ACTCON is the last response to a setpoint
command.
2.4.15 Use ACTTERM with Step
1 or 0
This parameter determines if an ACTTERM will be sent. If the parameter is set to
1, then step commands will issue an ACTTERM when the command is complete.
If the parameter is set to 0, ACTCON is the last response to a step command.