Backplane configuration – ProSoft Technology MVI56-104S User Manual

Page 28

background image

MVI56-104S ♦ ControlLogix Platform

Configuring the MVI56-104S Module

IEC 60870-5-104 Server Communication Module

User Manual


Page 28 of 188

ProSoft Technology, Inc.

November 18, 2009

2.2 [Backplane

Configuration]

This section provides the module with a unique name, identifies the method of
failure for the communications for the module if the processor is not in run, and
describes how to initialize the module upon startup.

2.2.1 Module

Name

0 to 80 characters

This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.

2.2.2 Read Register Start

Range 0 to 3999

This parameter specifies the starting register in the module where data will be
transferred from the module to the processor. Valid range for this parameter is 0
to 3999.

2.2.3 Read Register Count

0 to 4000

The Read Register Count parameter defines the size of the module’s input
database, up to a maximum value of 4000 words.

2.2.4 Write Register Start

0 to 3999

This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module.

2.2.5 Read Register Count

0 to 4000

The Read Register Count parameter defines the size of the module’s input
database, up to a maximum value of 4000 words.