Backplane configuration – ProSoft Technology MVI56-104S User Manual
Page 28

MVI56-104S ♦ ControlLogix Platform
Configuring the MVI56-104S Module
IEC 60870-5-104 Server Communication Module
User Manual
Page 28 of 188
ProSoft Technology, Inc.
November 18, 2009
2.2 [Backplane
Configuration]
This section provides the module with a unique name, identifies the method of
failure for the communications for the module if the processor is not in run, and
describes how to initialize the module upon startup.
2.2.1 Module
Name
0 to 80 characters
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.
2.2.2 Read Register Start
Range 0 to 3999
This parameter specifies the starting register in the module where data will be
transferred from the module to the processor. Valid range for this parameter is 0
to 3999.
2.2.3 Read Register Count
0 to 4000
The Read Register Count parameter defines the size of the module’s input
database, up to a maximum value of 4000 words.
2.2.4 Write Register Start
0 to 3999
This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module.
2.2.5 Read Register Count
0 to 4000
The Read Register Count parameter defines the size of the module’s input
database, up to a maximum value of 4000 words.