MVI56-104S ♦ ControlLogix Platform

Configuring the MVI56-104S Module

IEC 60870-5-104 Server Communication Module

User Manual


Page 34 of 188

ProSoft Technology, Inc.

November 18, 2009

2.4.8 w (latest ack threshold)

1 to 20

This parameter must match that of the host unit and specifies the number of
messages the module will receive before sending an S-format sequence
acknowledge message when no I-format data is ready to send. It is
recommended to set this value to 2/3 the value of k.

2.4.9 Time DB Offset

-1 or 0 to 3994

This parameter sets the location in the database where the module’s current date
and time will be copied to.

Note: The following tables lists the 12 byte, data area placed in the database if the Time DB Offset
parameter is set to a value other than -1:

Byte Length

Range

Description

0 to 1

2

0 to 59,999

Seconds and milliseconds

2

1

0 to 59

Minutes

3

1

0 to 23

Hour

4 1

Reserved

5

1

1 to 31

Day of the Month

6

1

1 to 12

Month

7 to 8

2

0 to 65,535

Year (four digit format, for example 2005)

9 1

Reserved

10

1

0 or 1

Invalid Flag (0 = Valid, 1 = Invalid

11 1

Reserved

2.4.10 Error Offset

0 to 3980

-1 to disable

This parameter sets the location in the module’s internal database when the
status and error information for the server will be stored. Enter a valid database
address of 0 to 3980 to store the information, or enter -1 to disable.