ProSoft Technology MVI56-104S User Manual
Page 163

Reference MVI56-104S
♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 163 of 188
November 18, 2009
5.6.4 Type identifier and cause of transmission assignments
(Station-specific parameters)
Shaded boxes: option not required
Black boxes: option not permitted in this companion standard
Blank boxes: functions or ASDU not used
Mark Type Identification/Cause of Transmission combinations: 'X" if only used in
standard direction, "R" if only used in reverse direction, and "B" if used in both
directions
1
2
3
4
5
6
7
8
9 10 11 12 13 20
to
36
37
to
41
44 45 46 47
<1>
M_SP_NA_1
X
X
X
X
X
<3>
M_DP_NA_1
X
X
X
X
X
<5>
M_ST_NA_1
X
X
X
X
X
<7>
M_BO_NA_1
<9>
M_ME_NA_1
X
X
X
X
<11>
M_ME_NB_1
X
X
X
X
<13>
M_ME_NC_1
X
X
X
X
<15>
M_IT_NA_1
X
X
X
X
<20>
M_PS_NA_1
<21>
M_ME_ND_1
<30>
M_SP_TB_1
X
X
X
<31>
M_DP_TB_1
X
X
X
<32>
M_ST_TB_1
X
X
X
<33>
M_BO_TB_1
<34>
M_ME_TD_1
X
X
X
<35>
M_ME_TE_1
X
X
X
<36>
M_ME_TF_1
X
X
X
<37>
M_IT_TB_1
X
X
X
<38>
M_EP_TD_1
<39>
M_EP_TE_1
<40>
M_EP_TF_1
<45>
C_SC_NA_1
X
X
X
X
X
<46>
C_DC_NA_1
X
X
X
X
X
<47>
C_RC_NA_1
X
X
X
X
X
<48>
C_SE_NA_1
X
X
X
X
X
<49>
C_SE_NB_1
X
X
X
X
X
<50>
C_SE_NC_1
X
X
X
X
X
<51>
C_BO_NA_1
X
X
X
X
X
<58>
C_SC_TA_1
X
X
X
X
X
<59>
C_DC_TA_1
X
X
X
X
X
<60>
C_RC_TA_1
X
X
X
X
X
<61>
C_SE_TA_1
X
X
X
X
X
<62>
C_SE_TB_1
X
X
X
X
X
<63>
C_SE_TC_1
X
X
X
X
X
<64>
C_BO_TA_1
<70>
M_EI_NA_1
X
<100>
C_IC_NA_1
X
X
X
X
X
<101>
C_CI_NA_1
X
X
X
<102>
C_RD_NA_1
X
<103>
C_CS_NA_1
X
X
<105>
C_RP_NA_1
X
X
<107>
C_TS_TA_1
X
X
<110>
P_ME_NA_1
X
X
<111>
P_ME_NB_1
X
X
<112>
P_ME_NC_1
X
X
<113>
P_AC_NA_1
<120>
F_FR_NA_1
<121>
F_SR_NA_1
<122>
F_SC_NA_1
<123>
F_LS_NA_1
<1124>
F_AF_NA_1
<125>
F_SG_NA_1
<126>
F_DR_TA_1
Cause of transmission
Type Identification