Invalid Bit Monitoring

This feature allows the application to set the invalid (IV) quality bit of the protocol
for all the monitored ASDU types supported. If the feature is enabled, the status
of each point configured by the user can have the individual IV quality bit
determined by the processor.

The parameters required to support this feature are:

Cyclic Set IV Time
IV Check Delay Time
IV Fail Count

To disable this feature, set the IV Fail Count parameter to 0. If the IV bit field is
absent or set to 0, the invalid quality state for the point will always be reported as
valid. If used, the Cyclic Set IV Time parameter must be at least 3 times larger
than the IV Check Delay Time.

The C

YCLIC

S

ET

IV

T

IME

parameter determines the interval at which the driver will

set all the IV bits for the points being monitored in the module. If the IV bit is ON
for the number of times specified by the IV

F

AIL

C

OUNT

parameter , the point is in

an invalid state. The driver will check the state of each bit at the frequency
determined by the IV

C

HECK

D

ELAY

T

IME

.

The values for the parameters must permit the driver to properly execute the
logic. For example, the value for C

YCLIC

S

ET

IV

T

IME

should be twice the IV

C

HECK

D

ELAY

T

IME

,

multiplied by the IV

F

AIL

C

OUNT

. If the cyclic timer is set to a

smaller value, the logic may not execute correctly.