Configuring the MVI56-104S Module

MVI56-104S ♦ ControlLogix Platform

User Manual

IEC 60870-5-104 Server Communication Module


ProSoft Technology, Inc.

Page 41 of 188

November 18, 2009

2.6.4 Sequence

Flag

In order to save bandwidth, you can configure the module to use the Sequence
Flag feature. If this feature is not selected, the module will send the object
address and its value at every monitored response to the master.

If this parameter is selected, the module will turn the Sequence Flag on every
monitored response sending the address for the first point along with all point
values. The master assumes that all other points use information object
addresses in a contiguous order (using the first point as the reference).