M_me_na_1 104, M_me_nb_1 104 – ProSoft Technology MVI56-104S User Manual
Page 44

MVI56-104S ♦ ControlLogix Platform
Configuring the MVI56-104S Module
IEC 60870-5-104 Server Communication Module
User Manual
Page 44 of 188
ProSoft Technology, Inc.
November 18, 2009
2.10 [M_ME_NA_1
104]
This section defines the monitored measured value, normalized database for the
server device emulated. This information is sourced from the database and is
transferred to the remote client unit. Each point occupies a word position in the
database. To determine the IOA (Information Object Address) for each object,
add the Point # in the following section to the value of the M_ME_NA parameter
offset parameter set in the previous section.
This section takes the following parameters:
Point
#:
DB
Address:
Group(s):
Default
Deadband:
IV DB Bit
Each point is one word and the DB Address value corresponds to the word offset
in the database.
2.11 [M_ME_NB_1
104]
This section defines the monitored measured value, scaled database for the
server device emulated. This information is sourced from the database and is
transferred to the remote client unit. Each point occupies a word position in the
database. To determine the IOA (Information Object Address) for each object,
add the Point # in the following section to the value of the M_ME_NB parameter
offset parameter set in the previous section.
This section takes the following parameters:
Point
#:
DB
Address:
Group(s):
Default
Deadband:
IV DB Bit
Each point is one word and the DB Address value corresponds to the word offset
in the database.