Maximum number of outstanding I format APDUs k and latest acknowledge
APDUs (w)
Parameter Default Value Remarks
Selected Value
k
12 APDUs
Maximum difference receive sequence number to
send state variable (Maximum value is 19)
w
8 APDUs
Latest acknowledge after receiving w I format
APDUs
Maximum range of values k: 1 to 32767 (2
15
-1) APDUs, accuracy 1 APDU
Maximum range of values w: 1 to 32767 (2
15
-1) APDUs, accuracy 1 APDU
(Recommendation: w should not exceed two-thirds of k).
Port number
Parameter Value
Remarks
Port number
2404
In all cases
RFC 2200 suite
RFC 2200 is an official Internet Standard which describes the state of
standardization of protocols used in the Internet as determined by the Internet
Architecture Board (IAB). It offers a broad spectrum of actual standards used in
the Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.
⌧ Ethernet
802.3
Serial
X.21
interface
Other selection from RFC 2200