MVI56-104S ♦ ControlLogix Platform

Configuring the MVI56-104S Module

IEC 60870-5-104 Server Communication Module

User Manual


Page 50 of 188

ProSoft Technology, Inc.

November 18, 2009

2.21 Ethernet

Configuration

Use this procedure to configure the Ethernet settings for your module. You must
assign an IP address, subnet mask and gateway address. After you complete
this step, you can connect to the module with an Ethernet cable.

1 Determine the network settings for your module, with the help of your network

administrator if necessary. You will need the following information:

o

IP address (fixed IP required) _____ . _____ . _____ . _____

o

Subnet mask

_____ . _____ . _____ . _____

o

Gateway address

_____ . _____ . _____ . _____

Note: The Gateway Address is optional, and is not required for networks that do not use a default
gateway.

2 Double-click the E

THERNET

C

ONFIGURATION

icon. This action opens the E

DIT

dialog box.

3 Edit the values for my_ip, netmask (subnet mask) and gateway (default

gateway).

4 When you are finished editing, click OK

to save your changes and return to

the ProSoft Configuration Builder window.