C_sc_na_1 104, C_dc_na_1 104 – ProSoft Technology MVI56-104S User Manual
Page 46

MVI56-104S ♦ ControlLogix Platform
Configuring the MVI56-104S Module
IEC 60870-5-104 Server Communication Module
User Manual
Page 46 of 188
ProSoft Technology, Inc.
November 18, 2009
2.14 [C_SC_NA_1
104]
This section defines the single point command database for the server emulated.
This information is sourced from the remote client and is transferred to the
database. Each point occupies a single bit position in the database. You can
associate a command with a monitored single-point database value to coordinate
the command/monitor operation. You must enter the correct Monitor Point # and
Monitor DB Address values in the table. If the Require Select parameter is not
set to zero, a select command must be received before an execute command will
be processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is one bit and the DB Address value corresponds to the bit offset in
the database.
2.15 [C_DC_NA_1
104]
This section defines the double point command database for the server
emulated. This information is sourced from the remote client and is transferred to
the database. Each point occupies two bits in the database. You can associate a
command with a monitored double point database value to coordinate the
command/monitor operation. You must enter the correct Monitor Point # and
Monitor DB Addr values in the table. If the Require Select parameter is not set to
zero, a select command must be received before an execute command will be
processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is two bits and the DB Address value corresponds to the bit offset in
the database.