ProSoft Technology MVI56-104S User Manual
Page 70
MVI56-104S ♦ ControlLogix Platform
Ladder Logic
IEC 60870-5-104 Server Communication Module
User Manual
Page 70 of 188
ProSoft Technology, Inc.
November 18, 2009
9958 GMT Time Event Write Block Format
Here is the Write Block format for Block ID 9958 that moves GMT formatted time-
stamped events.
Word Offset in Block Data Field(s)
Description
0
Write Block ID
This field contains the value of 9958 identifying the block
type to the module.
1
Event Count
Number of events present in the block. Valid Values: 1 to
10.
2
Event #1
Event data to add to event message queue.
17
Event #2
Event data to add to event message queue.
32
Event #3
Event data to add to event message queue.
47
Event #4
Event data to add to event message queue.
63
Event #5
Event data to add to event message queue.
79
Event #6
Event data to add to event message queue.
95
Event #7
Event data to add to event message queue.
111
Event #8
Event data to add to event message queue.
127
Event #9
Event data to add to event message queue.
143
Event #10
Event data to add to event message queue.