5.2.3 Using Control (Command) Points
The following control points are supported by the MVI56-104S module:
Symbol Description
C_SC_NA Single-Point
Command
C_DC_NA Dual-Point
Command
C_RC_NA Step-Point
Command
C_SE_NA
Measured Normalized Point Command
C_SE_NB
Measured Scaled-Point Command
C_SE_NC
Measured Short Floating-Point Command
Each control point is identified by its Information Object Address. For each
control point, configure the following parameters:
Point #: This is the information object address of the point. It identifies the point
in the network. This address must be unique for each Common ASDU Address in
the network.
DB Address: This is the database location in the MVI56-104S module
associated with the point.
Monitor Point #-Monitor DB Address- The user might (optionally) configure a
monitor point to be sent by the MVI56-104S module when it receives the
command for that specific point.