ProSoft Technology MVI56-104S User Manual
Page 132
MVI56-104S ♦ ControlLogix Platform
Reference
IEC 60870-5-104 Server Communication Module
User Manual
Page 132 of 188
ProSoft Technology, Inc.
November 18, 2009
Deadbands
The monitored measured points (M_ME_NA and M_ME_NB) will generate
events only if the data value changes an amount greater than or equal to the
configured deadband value.
For example, with the following point configured:
If the current value for this point is 130, it would only generate events if:
NEW VALUE is less than or equal to 30
OR
NEW VALUE is greater than or equal to 230.
You can set the deadband for each monitored measured point through the
configuration file.