ProSoft Technology MVI56-104S User Manual
Page 137

Reference MVI56-104S
♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 137 of 188
November 18, 2009
If this parameter is set to 0, the module will not generate events for any points. A
non-zero value will configure how frequently the module will scan for events in
the database.
Point Level
You can configure if each point should generate events or not using the Group
field for each point configuration. The user should set the value as 40000000 in
order to disable the generation of events for that specific point.
Data Type Level
The user may configure if a data type should generate events or not. Each data
type has a configuration parameter to control the generation of events:
In the example above, only the M_SP_NA points would generate events.