Configuring the MVI56-104S Module

MVI56-104S ♦ ControlLogix Platform

User Manual

IEC 60870-5-104 Server Communication Module


ProSoft Technology, Inc.

Page 29 of 188

November 18, 2009

2.2.6 Failure

Flag

Count

0 through 65535

This parameter specifies the number of successive transfer errors that must
occur before halting communication on the application port(s). If the parameter is
set to 0, the application port(s) will continue to operate under all conditions. If the
value is set larger than 0 (1 to 65535), communications will cease if the specified
number of failures occur.

2.2.7 Error

Offset

0 to 3980, or -1 to disable

This parameter specifies the database location where to write status data.

2.2.8 Initialize Output Data

Yes or No

This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to No (0), the output data will
be initialized to 0. If the value is set to Yes (1), the data will be initialized with
data from the processor. Use of this option requires associated ladder logic to
pass the data from the processor to the module.