ProSoft Technology MVI56-104S User Manual
Page 31

Configuring the MVI56-104S Module
MVI56-104S ♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 31 of 188
November 18, 2009
2.3.1 NTP Server IP Address
Enter in dotted notation
This parameter sets the IP address of the NTP server to utilize for time
acquisition. Select an NTP server with the greatest accuracy that can be
accessed all the time from your network. Setting this IP address to 0.0.0.0
disables SNTP server requests.
2.3.2 Time
Zone
-11 to 11
This parameter specifies the time zone offset to be used from the UTC time
zone. A value of zero uses UTC time. If the value entered is positive, the time
zone is west of the UTC time zone (that is, Eastern Standard Time is 5). If the
value entered is negative, the time zone is east of the UTC time zone (that is,
Continental Europe is -1).
2.3.3 Use Daylight Savings Time
Yes or No
This parameter specifies if daylight savings time will be used in the time
computation.
2.3.4 Database
Register
-1 or 0 to 3992 as an even value
This parameter specifies if the NTP time computed by the driver is to be placed
into the module’s database. If a value of -1 is specified, the time will not be
placed into the database. If the value is between 0 and 3992, the time will be
placed in the database. The first 4 bytes will represent the seconds since
1/1/1970, and the second 4 bytes will represent the number of microseconds. An
even value should be used for the register value in order for the data to be stored
correctly.