beautypg.com

ProSoft Technology MVI56-104S User Manual

Page 105

background image

Reference MVI56-104S

♦ ControlLogix Platform

User Manual

IEC 60870-5-104 Server Communication Module


ProSoft Technology, Inc.

Page 105 of 188

November 18, 2009

5.2.2 Using

Monitor

Points

The following monitor points are supported by the MVI56-104S module:

Symbol

Description

Data Size in
Database

Addressing Type

M-SP-NA

Monitored Single-Points

1 bit

Bit

M-DP-NA

Monitored Dual-Points

2 bits

Bit

M-ST-NA

Monitored Step-Points

1 byte

Byte

M-ME-NA

Monitored Measured Normalized-Points

1 word

Word

M-ME-NB

Monitored Measured Scaled-Points

1 word

Word

M-ME-NC

Monitored Measured Short Floating Points

2 words

Double-Word

M-IT-NA

Monitored Counter-Points

2 words

Double-Word

Each monitor point is identified by its Information Object Address (it should be
unique for each Common ASDU Address in the network). For each monitor point,
configure the following parameters:

Point # - The information object address of the point. It identifies the point in the
network.

DB Address - The database location in the MVI56-104S module associated with
the point. You must associate each point to a database address in the MVI56-
104S module. The interpretation of this parameter depends on the point type
configured. For example, for an M_SP_NA point, this value represents the bit
address. For a M_ME_NA point, this value represents the Word address.

Group(s) - This is the group definition for the point. It sets how the point will be
polled by the master (cyclic or group interrogation). It can also be used to enable
or disable the event generation for one specific point. The group parameter is
discussed in the Data Communication section.

Deadband - Sets the deadband for each Measured point. If the value changes
from more than the configured deadband , the module will generate an event for
this point.

IV DB Bit - This feature allows the application to set the invalid (IV) quality bit of
the protocol for all the monitored ASDU types supported. If you enable this
feature, the processor can determine the individual IV quality bit status of each
point you configured.