MVI56-104S ♦ ControlLogix Platform

Configuring the MVI56-104S Module

IEC 60870-5-104 Server Communication Module

User Manual


Page 40 of 188

ProSoft Technology, Inc.

November 18, 2009

2.6.3 Point

Count

Point Count configuration ranges in the following configuration items are based
on the assumption that you will be using only one of the available data types for
your application. The number of point counts you configure will have an effect on
module performance, in particular the accuracy of the module’s internal clock.

M_SP_NA point count: This parameter specifies the number of point values

assigned in monitored single-point database. Range is 0 to 1000.

M_DP_NA point count: This parameter specifies the number of point values

assigned in monitored dual-point database. Range is 0 to 1000.

M_ST_NA point count: This parameter specifies the number of point values

assigned in monitored step-point database. Range is 0 to 1000.

M_ME_NA point count: This parameter specifies the number of point values

assigned in monitored normalized-point database. Range is 0 to 1000.

M_ME_NB point count: This parameter specifies the number of point values

assigned in monitored scaled-point database. Range is 0 to 1000.

M_ME_NC point count: This parameter specifies the number of point values

assigned in monitored scaled short-float point database. Range is 0 to 50.

M_IT_NA point count: This parameter specifies the number of point values

assigned in monitored counter-point database. Range is 0 to 99.

C_SC_NA point count: This parameter specifies the number of point values

assigned in command single-point database. Range is 0 to 1000.

C_DC_NA point count: This parameter specifies the number of point values

assigned in command dual-point database. Range is 0 to 1000.

C_RC_NA point count: This parameter specifies the number of point values

assigned in command step-point database. Range is 0 to 1000.

C_SE_NA point count: This parameter specifies the number of point values

assigned in command normalized-point database. Range is 0 to 1000.

C_SE_NB point count: This parameter specifies the number of point values

assigned in command scaled-point database. Range is 0 to 1000.

C_SE_NC point count: This parameter specifies the number of point values

assigned in command short-float point database. Range is 0 to 50.