Command Points Addressing
As discussed before, the command points must be configured in a database area
that is updated at the module. You must associate each point to a database
address in the MVI56-104S module. The interpretation of this parameter depends
on the point type configured.
C_SC_NA and C_DC_NA
The single-point command and dual-point command points use one bit with bit-
addressing. For example, if you configure the following points:
These points would be used as follows:
Inf. Object Address
Module Database Address
100
Bit 0 of word 100
101
Bit 1 of word 100
102
Bit 2 of word 100