M_sp_na_1 104, M_dp_na_1 104, M_st_na_1 104 – ProSoft Technology MVI56-104S User Manual
Page 43

Configuring the MVI56-104S Module
MVI56-104S ♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 43 of 188
November 18, 2009
2.7 [M_SP_NA_1
104]
This section defines the monitored single-point database for the server device
emulated. This information is sourced from the database and is transferred to the
remote client unit. Each point in the database occupies 1 bit (1 = On, 0 = Off
state).
This section takes the following parameters:
Point
#
DB
Address
Group(s)
IV DB Bit
Each point is one bit and the DB address value corresponds to the bit offset in
the database.
2.8 [M_DP_NA_1
104]
This section defines the monitored dual-point database for the server device
emulated. This information is sourced from the database and is transferred to the
remote client unit. Each point in the database occupies two bits (00 =
intermediate, 01 = off, 10 = on and 11 = intermediate).
This section takes the following parameters:
Point
#:
DB
Address:
Group(s):
IV DB Bit
Each point is two bits and the DB address value corresponds to the bit offset in
the database.
2.9 [M_ST_NA_1
104]
This section defines the monitored step database for the server device emulated.
This information is sourced from the database and is transferred to the remote
client unit. Each point in the database occupies one byte.
This section takes the following parameters:
Point
#:
DB
Address:
Group(s):
IV DB Bit
Each point is one byte and the DB Address value corresponds to the byte offset
in the database.