2.18 [C_SE_NB_1

104]

This section defines the scaled setpoint database for the server emulated. This
information is sourced from the remote client and is transferred to the database.
You can associate a command with a monitored scaled database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # and Monitor DB Addr values in the table. If the Require Select parameter
is not set to zero, a select command must be received before an execute
command will be processed.

This section takes the following parameters:

Point

#:

DB

Address:

Monitor

Point

#:

Monitor

DB

Addr:

Require

Select:

Each point is one word and the DB Address value corresponds to the word offset
in the database.

2.19 [C_SE_NC_1

104]

This section defines the short-float setpoint database for the server emulated.
This information is sourced from the remote client and is transferred to the
database. Each point occupies a double-word position in the database. If the
Require Select parameter is not set to zero, a select command must be received
before an execute command will be processed.

This section takes the following parameters:

Point

#:

DB

Address:

Monitor

Point

#:

Monitor

DB

Addr:

Require

Select:

Each point is two words and the DB Address value corresponds to the double-
word offset in the database.