C_se_nb_1 104, C_se_nc_1 104 – ProSoft Technology MVI56-104S User Manual
Page 48

MVI56-104S ♦ ControlLogix Platform
Configuring the MVI56-104S Module
IEC 60870-5-104 Server Communication Module
User Manual
Page 48 of 188
ProSoft Technology, Inc.
November 18, 2009
2.18 [C_SE_NB_1
104]
This section defines the scaled setpoint database for the server emulated. This
information is sourced from the remote client and is transferred to the database.
You can associate a command with a monitored scaled database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # and Monitor DB Addr values in the table. If the Require Select parameter
is not set to zero, a select command must be received before an execute
command will be processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is one word and the DB Address value corresponds to the word offset
in the database.
2.19 [C_SE_NC_1
104]
This section defines the short-float setpoint database for the server emulated.
This information is sourced from the remote client and is transferred to the
database. Each point occupies a double-word position in the database. If the
Require Select parameter is not set to zero, a select command must be received
before an execute command will be processed.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Require
Select:
Each point is two words and the DB Address value corresponds to the double-
word offset in the database.