ProSoft Technology MVI56-104S User Manual
Page 53

Configuring the MVI56-104S Module
MVI56-104S ♦ ControlLogix Platform
User Manual
IEC 60870-5-104 Server Communication Module
ProSoft Technology, Inc.
Page 53 of 188
November 18, 2009
Select the
1756-M
ODULE
(Generic 1756 Module) from the list and click OK.
This action opens the N
EW
M
ODULE
dialog box.
Enter the Name, Description and Slot options for your application. You must
select the C
OMM
F
ORMAT AS
D
ATA
-
INT in the dialog box, otherwise the
module will not communicate over the backplane of the ControlLogix rack.
Click OK to continue.
2 Edit the Module Properties. Select the R
EQUESTED
P
ACKET
I
NTERVAL
value
for scanning the I/O on the module. This value represents the minimum
frequency that the module will handle scheduled events. This value should
not be set to less than 1 millisecond. The default value is 5 milliseconds.
Values between 1 and 10 milliseconds should work with most applications.