Configuring the MVI56-104S Module

MVI56-104S ♦ ControlLogix Platform

User Manual

IEC 60870-5-104 Server Communication Module


ProSoft Technology, Inc.

Page 53 of 188

November 18, 2009

Select the

1756-M

ODULE

(Generic 1756 Module) from the list and click OK.

This action opens the N

EW

M

ODULE

dialog box.

Enter the Name, Description and Slot options for your application. You must
select the C

OMM

F

ORMAT AS

D

ATA

-

INT in the dialog box, otherwise the

module will not communicate over the backplane of the ControlLogix rack.
Click OK to continue.

2 Edit the Module Properties. Select the R

EQUESTED

P

ACKET

I

NTERVAL

value

for scanning the I/O on the module. This value represents the minimum
frequency that the module will handle scheduled events. This value should
not be set to less than 1 millisecond. The default value is 5 milliseconds.
Values between 1 and 10 milliseconds should work with most applications.