Using a BMK: Monitoring

Info: The AH I/O display correlates with the SETUP: 05B AmpHour Size setting to help

determine the 05B Battery SOC display.
Example: if you run a 10-amp load for three hours, the display will show -30 AH. When

you begin charging, the display will count from -30 AH back toward 0 AH.

• 05F

Reset

AH

Out

– This meter displays the total amp-hours removed from the battery

since it was last reset. This display can be used as a battery load indicator to help identify and

monitor the battery load consumption. The range is 0 to 65,535.0 amp-hours (0.1 amp-hour

resolution). To reset the AH value to zero, press and hold the rotary SELECT knob for three

seconds when the Reset AH Out display is shown. After this display has been reset, it will begin

calculating and displaying new rAH out values. This display automatically resets to zero if the

sense module is disconnected from power.

• 05G Total AH Out – This meter displays the total amp-hours removed from the battery since

the sense module was fi rst connected. This display can be used as a battery service life indi-

cator. The value is displayed in 0.1k [or 100 AH (“k” equals 1000)] resolution up to a maxi-

mum of 6,553.5k AH (6,553,500 amp-hours). To reset this display, press and hold the rotary

SELECT knob for three seconds while the Total AH Out display is shown. After this value has

been reset, the display will begin monitoring and showing new total AHr out values. Also, the

displayed number resets to 0.0k when the sense module is disconnected from power.

• 05H

Minimum

VDC

– This menu displays the lowest battery voltage since the last reset. The

voltage shown on the display is averaged each second, and is helpful when troubleshooting or

detecting an over-discharge condition. To reset this display, press and hold the rotary SELECT

knob for three seconds while the Minimum VDC display is shown. After this value has been

reset, the display will begin monitoring and showing new minimum DC input values. If the

battery monitor is not connected or not communicating, the display will show “0.0”.

• 05I Maximum VDC – This menu displays the highest battery voltage since the last reset.

The voltage shown on the display is averaged each second, and this allows you to check your

charging system (battery charger, charge controller, etc.,) to ensure the charging voltage has

been attained. This display is also helpful when troubleshooting or detecting if an over-charge

condition has occurred. To reset this display, press and hold the rotary SELECT knob for three

seconds while the Maximum VDC display is shown. After this value has been reset, the display

begins monitoring and showing new maximum DC input values. If the battery monitor is not

connected or not communicating, the display shows “0.0”.

• 05J Days Since 100% SOC – This read-only menu displays the number of days since the

battery was at 100% SOC, and is calculated in the remote.

Info: This display resets: once the battery SOC reaches 100%, power to the remote is

lost, or communication from the BMK is lost.

Info: This display uses information from the METER: 05B Battery SOC menu to

determine the last time the battery SOC was at 100%.

Info: For the ‘days since value’ to increment, the METER: 05B Battery SOC display

must have a valid SOC number (Think’n, No Comm or any BMK fault is not valid), and

the SETUP: 04K Gen 100% SOC Start Days must be enabled (not set to OFF).
Info: This display is similar to the METER: 04F Since 100% menu (calculated in AGS).

If an AGS is installed at a later date (or the remote is reconnected), the two menus

are not coordinated with each other. However, they automatically synchronize once

the BMK’s METER: 05B Battery SOC menu reaches 100% SOC (or you can manually

synchronize by momentarily removing the network cable from the BMK).