beautypg.com

Setup – Magnum Energy ME-ARC Remote User Manual

Page 24

background image

© 2014 Magnum Energy, Inc.

Page 17

Setup

STANDBY MODE

Current from the grid/generator to the inverter’s

AC input is used to power the inverter’s AC loads

and to charge the battery.

Example below:

 Current to inverter input (AC Input)

= 20 Amps AC

 Current to power the AC loads (AC Load)

= 10 Amps AC

 Current to charge battery (Inv/Chg Amps)

= 10 Amps AC

MAGNUM

INVERTER

AC Input =

20 Amps AC

A

AC Load =

10 Amps AC

Inv/Chg Amps=

10 Amps AC

A

Inverter

Amp meters

=

A

A

AC CURRENT
(GRID/GEN)

DC CURRENT

(BATTERY)

INVERTER

AC LOADS

120ADC

TO

BATT

-20AAC

.

FROM

GRID

10AAC

.

TO

LOADS

.

LOAD SUPPORT MODE

(MSH Series Only)

The MSH Series uses current from the battery to

assist in powering the

inverter’s AC loads

and to

reduce the current from the grid/generator.

Example below:

 Current to inverter input (AC Input)

= 10 Amps AC

 Current to power the AC loads (AC Load)

= 20 Amps AC

 Current from battery (Inv/Chg Amps)

= -10 Amps AC

MSH SERIES

INVERTER

AC Input =

10 Amps AC

A

AC Load =

20 Amps AC

Inv/Chg Amps=

-10 Amps AC

A

Inverter

Amp meters

=

A

A

AC CURRENT
(GRID/GEN)

DC CURRENT

(BATTERY)

INVERTER

AC LOADS

-120ADC

FROM

BATT

-10AAC

.

FROM

GRID

20AAC

.

TO

LOADS

.

INVERT MODE

Current from the battery is used by the inverter

to power the inverter’s AC loads.

Example below:

 Current to inverter input (AC Input)

= 0 Amps AC

 Current from battery (Inv/Chg Amps)

= -10 Amps AC

 Current to power the AC loads (AC Load)

= 10 Amps AC

MAGNUM

INVERTER

AC Input =

0 Amps AC

A

AC Load =

10 Amps AC

Inv/Chg Amps=

-10 Amps AC

A

Inverter

Amp meters

=

A

A

AC CURRENT
(GRID/GEN)

DC CURRENT

(BATTERY)

INVERTER

AC LOADS

-120ADC

.

FROM

BATT

0AAC

FROM

GRID

10AAC

TO

LOADS

02C Input Amps

0 Amps AC

02D Inv/Chg Amps

-10 Amps AC

02B Load Amps

10 Amps AC

02C Input Amps

20 Amps AC

02B Load Amps

10 Amps AC

02D Inv/Chg Amps

10 Amps AC

02C Input Amps

10 Amps AC

02B Load Amps

20 Amps AC

02D Inv/Chg Amps

-10 Amps AC

Figure 3-8, Current Flow – Load Support Mode

Figure 3-6, Current Flow – Inverter Mode

Figure 3-7, Current Flow – Standby Mode