Using an AGS Module: Operation/Monitoring

7.2.6

AGS Remote Status Messages

A status message may be an operational or fault message. Access the AGS status menu (METER:

04A AGS Status menu) to view the AGS’s current operating status. This menu is important when

determining if the AGS is working correctly, or for troubleshooting an AGS installation.

7.2.6.1 AGS Remote Operational Statuses

Table 7-3 below has a brief description of possible AGS operational statuses.

Status

Description

AC In

The inverter/charger is connected to another source such as a grid or an

alternate generator, and is not controlled by the AGS. When AC In displays,

the AGS is prevented or locked out from all autostarting conditions, except

for when the generator needs to exercise—if enabled.

Gen Cooldown

The autostop setting has been met in one of the generator autostart/au-

tostop menus and the generator has been disconnected from the inverter/

charger. However, the generator still runs until the cooldown time is met

(as per the SETUP: 04J Gen Cooldown Time setting).

Gen Warmup

The AGS is attempting to start the generator and a time period has been

set from the SETUP: 04I Gen Warm-up Time menu. Once the AGS status

indicates “Warm-up”, the inverter/charger’s AC input ignores any incoming

AC power. This prevents the inverter/charger from loading the generator

during warm-up. Once the AGS has determined that the generator is run-

ning, the warm-up time setting must be met before the generator can con-

nect to the inverter/charger.

Manual Run

Generator started manually from a start/stop switch directly connected to

the generator, or from the CTRL: 03 Gen Control menu.

Note: The AGS determines that the generator has been manually turned on by sensing a gen

run sense voltage to Terminal #2 on the AGS’s 8-port terminal block. However, if the Gen Type

DIP switch is set to “2-Wire Standby” (which doesn’t require a gen run sense voltage), manually

turning the generator on displays a status of “AC In” rather than “Manual Run”.

No Comm

The AGS is not communicating with the inverter/remote.

AGS not present

If an AGS is installed, then refer to Section 7.3.2 “Resolving AGS Opera-

tional Statuses” for assistance.

Off

The CTRL: 03 Gen Control menu is set to OFF. This setting will not allow the

AGS to autostart the generator.

Quiet Time

The AGS has entered Quiet Time per the SETUP: 04G Quiet Time setting.

Note: The generator will not autostart during Quiet Time.
Ready

The CTRL: 03 Gen Control menu is set to AUTO, and the AGS is ready to

autostart the generator based on the active autostart settings under the

SETUP: 04 AGS Setup menus.

Table 7-3, AGS Remote Operational Statuses