beautypg.com

Magnum Energy ME-ARC Remote User Manual

Page 114

background image

© 2014 Magnum Energy, Inc.

Page 107

Using a PT Controller: Setup

◊ Relay Disengage DelayThis setting determines how long the Relay Disengage Volts

parameter must be continuously maintained before the Aux Relay disengages. Use this set-

ting to delay the time that the Aux Relay disengages once the battery voltage trip point has

been reached—so the Aux Relay does not cycle unnecessarily.
Default setting: 10 Sec
Range: 0-127 Sec, 1-127 Min (1-sec increments up to 127 sec, then 1-min increments)

• 06G PT Alarm The alarm in the PT controller can be programmed to be a high or low bat-

tery voltage alarm when VDC is selected from the CTRL: 04C PT Alarm Control menu. Use the

following settings to adjust the battery voltage levels (with an adjustable delay) that deter-

mine when the alarm turns on and off.
◊ Set Alarm ON VoltsThis setting is the battery voltage trip point at which the Alarm

ON Delay time begins. Once the battery voltage has reached this setting continuously for the

duration of the Alarm ON Delay setting, the alarm will turn on. This setting can be below or

above the Alarm OFF Volts setting, depending on if you want the alarm to work as active low

or active high.
Default setting: 10.0 VDC (12V), 20.0 VDC (24V), 40.0 VDC (48V)
Range: 8.0-16.6 (12V), 16.0-33.2 (24V), 32.0-66.4 (48V)
◊ Set Alarm ON DelayThis setting determines how long the Alarm ON Volts parameter

must be continuously maintained before the alarm turns on. Use this setting to delay the time

that the alarm turns on once the battery voltage trip point has been reached—so the alarm

does not turn on unnecessarily.
Default setting: 10 Sec
Range: 0-127 Sec, 1-127 Min (1-sec increments up to 127 secs, then 1-min increments)
◊ Set Alarm OFF VoltsThis setting is the battery voltage trip point at which the Alarm

OFF Delay time begins. Once the battery voltage has reached this setting continuously for the

duration of the Alarm OFF Delay setting, the alarm will turn off. This setting can be below or

above the Alarm ON Volts setting, depending on if you want the alarm to work as active low

or active high.
Default setting: 14.0 VDC (12V), 28.0 VDC (24V), 56.0 VDC (48V)
Range: 8.0-16.6 (12V), 16.0-33.2 (24V), 32.0-66.4 (48V)
◊ Set Alarm OFF DelayThis setting determines how long the Alarm OFF Volts parameter

must be continuously maintained before the alarm turns off. Use this setting to delay the time

that the alarm turns off once the battery voltage trip point has been reached—so the alarm

does not turn off unnecessarily.
Default setting: 10 Sec
Range: 0-127 Sec, 1-127 Min (1-sec increments up to 127 secs, then 1-min increments)

• 06H PowerSave PT Display The PowerSave feature is provided to conserve energy by

turning off any indicator that is not needed. While the PT controller is in the PowerSave mode,

the period (or decimal) of each LED segment (3 periods total) comes on one at a time (from

left to right, then right to left). The rest of the PT display and its four relevant LED indicators

are off to conserve energy. During the day—while charging—the charger status LED will still

be on during PowerSave; at nighttime—since there is no charging—the charger status LEDs

will be off.
The controller goes into PowerSave mode if there hasn’t been a button press or fault message

for a set period of time, depending on the setting (15 Min is the default setting). Whenever

the controller goes into PowerSave mode, the display and its relevant LEDs can be reactivated

by pressing any pushbutton.
If the AUX relay is energized, the AUX LED will remain on during PowerSave mode. If there

is a fault during PowerSave, the display and Fault LED will come on and stay on as long as a

fault is active.
Default setting: 15 Min
Range: OFF, 1-60 Min (1-min increments)