Page 23

Setup

Where should I set AC In - VDC? Check with your battery manufacturer to determine the

correct settings for your batteries. Typically, manufacturers do not recommend discharging the

batteries below 50% (i.e., a voltage setting of approximately 12.0-12.2 VDC, 24.0-24.4 VDC and

48-48.8 VDC for 12, 24, and 48-volt batteries, respectively). To protect the batteries from over-

discharging, set to 12.2 VDC (12v), 24.4 VDC (24v), or 48.8 VDC (48v).
Set the disconnect voltage setting higher than the absorb voltage setting in order to reduce cy-

cling of the system. A setting higher than the absorb voltage requires the energy source (solar,

wind, etc.,) to raise the DC voltage above the charger settings. This ensures the battery gets at

least an 80-85% charge (preferably 100%) before the AC is disconnected and the inverter re-

sumes powering from the batteries.
• 02E AC In - SOC – These settings determine when the inverter automatically connects/

disconnects the incoming utility power based on the State of Charge (SOC) of the inverter’s

battery bank.
◊ Connect SOC – This setting determines at what battery SOC% the inverter/charger con-

nects to incoming utility power and transfers the loads from the inverter battery power to the

utility grid.
Default setting: 80% SOC
Range: 20-99%
◊ Disconnect SOC – Once the inverter has connected to the incoming AC—based on the

SOC Connect setting—this setting determines at what battery SOC% the inverter/charger

disconnects from incoming utility power and resumes powering the loads from the inverter’s

battery power.
Default setting: 100% SOC
Range: 21-100%

Info: If Connect SOC is selected and the incoming AC connects, the router issues

a one-time “Start Bulk” command to the inverter/charger. This ensures the charger

enters the Bulk/Absorb charge cycle regardless of battery voltage.

Info: The transfer to/from incoming AC occurs immediately when the Connect SOC or

Disconnect SOC setting is reached.

Info:

A ME-BMK is required in order to use the 02E AC In - SOC setting. If this setting

is established and there is no ME-BMK installed in the system, or if a valid SOC number

is not displayed under the METER: 05 BMK Meters/05B Battery SOC menu (i.e., Think’n,

No Comm, Power-up Fault and Factory Fault are not valid SOC numbers), then the

inverter will not connect to the incoming AC power.

What is the AC In - SOC feature? This feature allows the inverter/charger system to automati-

cally switch between utility connected and standalone battery operation based on the inverter’s

battery SOC (per the ME-BMK battery monitor). When using this feature, the inverter loads are

normally powered from the battery and a solar array (or wind, and/or hydro). In the event the

solar array cannot deliver enough power and the battery’s SOC drops to the Connect SOC setting,

the inverter connects to the utility to continue powering the loads connected to the inverter’s out-

put and to charge the battery. Once the solar array can again deliver enough power to charge the

battery to the Disconnect SOC setting, the inverter disconnects from the utility and again powers

the inverter loads from the battery.
Where should I set AC In - SOC? Check with your battery manufacturer to determine the cor-

rect settings for your batteries. For the Connect SOC setting, most manufacturers do not recom-

mend discharging the batteries below 50% to maintain the life of the battery. Set the Disconnect

SOC value to get at least an 80-85% charge (preferably 100%) before the AC is disconnected and

the inverter resumes powering from the batteries.

Info:

When using the AC In - SOC setting, ensure the SETUP: 03D Absorb Done SOC

setting is higher than the Disconnect SOC setting or the inverter may not disconnect

from the incoming AC because the battery may not be charged to a high enough SOC

level to meet the Disconnect SOC setting.