Using an AGS Module: Operation/Monitoring

METER: 04A AGS Status Menu
This read-only menu displays the AGS’s current status. There are 28 different status messages

that can display to identify what state the AGS is currently in—only one displays at any one time

(refer also to Figure 7-2).

Info: This menu is important when determining if the AGS is working correctly or for

troubleshooting an AGS installation. For any fault mode displayed in the status menu,

refer to Section 7.3.3.

Available statuses are (see Tables 7-3 through 7-5 for information on each):
Operational/Start Status:
• AC

In

• Gen

Cooldown

• Gen

Warmup

• Manual

Run

• No Comm (AGS not present)
• Off

• Start

Test

• Start

Time

• Start

Topoff

• Start

VDC

• Start 100% SOC

• Quiet

Time

• Ready
• Start

Amp

• Start

Exercise

• Start

SOC

• Start

Temp

Fault Status:
• Fault

Amp

• Fault

Exercise

• Fault Gen Run
• Fault

MaxRn

• Fault

SOC

• Fault

Temp

• Fault

Test

• Fault

Time

• Fault

Topoff

• Fault

VDC

• Fault 100% SOC

METER: 04B DC Volts-AGS Menu
This read-only menu displays the DC voltage measured at Terminals #3 and #4 of the AGS con-

troller. This menu is useful in setting up the voltage start for the AGS, and for troubleshooting its

operation.

Info: This DC voltage reading may vary from the DC voltage readings in the METER:

01A DC Volts and METER: 05C DC Volts-BMK menu items. When troubleshooting, read

the appropriate related meter for each device. Use this menu for AGS verifi cation and

testing.

METER: 04C Gen Run Time Menu
This read-only menu displays the length of time the generator has been running since it was

autostarted. This helps determine how long the generator has been running since it was auto-

started—in case you were not present when it started. This menu is enabled when CTRL: 03 Gen

Control is set to AUTO, but does not display run time when the generator has been manually

started. This meter is not designed to replace an hour meter that shows the total hours the gen-

erator has run—refer to the METER: 04G Hour Meter menu.

Info: The Gen Run Time menu’s timer is started when the gen run sense voltage/signal

is correct and qualifi ed at the AGS controller. It is not considered qualifi ed until after

a full start attempt and the 04I Gen Warm-up Time setting is satisfi ed. Cooldown and

warm-up times are not included in the gen run time display. Total generator run time

= Gen Run Time + Gen Warm-up Time + Gen Cooldown.

Info: The times in this display are shown in tenths of an hour (0.0 hrs., 0.1 hrs.,

etc.,)—thus, 0.1 hrs. = 6 minutes.

Info: Depending on the AGS’s version, the Gen Run Time display resets to 0.0 differ-

ently. The ME-AGS-N (Ver 5.2): resets to 0.0 when the generator autostart has fi nished.

The ME-AGS-N (≥Ver 5.3): resets to 0.0 when another generator autostart is triggered.

Info: This display is used by the SETUP: 04F Max Gen Run Time menu to determine the

generator’s maximum run time when started automatically.