beautypg.com

3 pt remote fault statuses – Magnum Energy ME-ARC Remote User Manual

Page 127

background image

Page 120

© 2014 Magnum Energy, Inc.

Using a PT Controller: Operation/Monitoring

10.2.4.3 PT Remote Fault Statuses

The following “Fault” statuses (Table 10-4) display on the remote to indicate that the PT is not

operating as intended. Refer to Section 10.3.2 for help in diagnosing/resolving the problem.
Note: The fault codes (example: “F12”) listed below only appear on the PT’s LCD display to iden-

tify the particular PT fault. These fault codes do not appear on the ME-ARC remote’s LCD display.

Table 10-4, PT Remote Fault Statuses

Status

Description

No PV Input-PT

(F01)

The PT controller turned off because there has been no source of PV pow-

er detected on the PV terminals (i.e., PV+ to PV-) for more than 24 hrs.

Int Pwr Sup-PT

(F02)

The PT controller turned off because the voltage from the auxiliary power

supply in the controller has dropped to a low level.

High PV VDC-PT

(F03)

The PT controller turned off because a very high PV voltage (>187 VDC)

has been detected on the PV terminals (i.e., PV+ to PV-).

High Bat VDC-PT

(F04)

The PT controller turned off due to instantaneous high voltage (≥68 VDC)

detected on the battery terminals (i.e., BAT+ to BAT-).

BTS Shorted-PT

(F05)

The PT controller continues to run, but a problem with the BTS has been

detected (temp sensor has shorted). When this happens, the temp-com-

pensation is fi xed at a temperature of 77°F/25°C.

FET Overtemp-PT

(F06)

The PT controller turned off because the internal FETs (Field Effect Tran-

sistors) have exceeded their safe operating temperature (≥85˚C/185˚F).

HiBatt Temp-PT

(F07)

The PT controller turned off because the BTS has reached a very high

temperature (≥55˚C/≥131˚F).

Int Overload-PT

(F08)

The PT controller turned off because the current to an internal sensor has

exceeded the controller’s protection limits.

Int Phase-PT

(F09)

The PT controller turned off because one of the internal phases is faulty

or the phase signals are not in sync with each other.

BTS Open-PT

(F10)

The PT controller continues to run, but the BTS has opened or is no lon-

ger connected. When this happens, the temp-compensation is fi xed at a

temperature of 77°F/25°C.

Int Power-PT

(F11)

The PT controller turned off because the internal power control circuitry

reached its protection limits.

Ground Fault-PT

(F12)

The PT controller turned off because the GFP fuse has opened due to a

ground-fault condition.

ARC Fault-PT

(F13)

The PT controller turned off because a series ARC fault has been detected.

Int NTC-PT

(F14)

The PT controller turned off because the internal NTC (Negative Tem-

perature Coefficient) temperature sensor suddenly caused a large, unex-

pected temperature change.

Int Hardware-PT

(F15)

The PT controller turned off because a redundant hardware protection

circuit that monitors the internal temperature has exceeded a safe oper-

ating limit.

Ind Overtemp-PT

(F16)

The PT controller turned off because the charger’s inductors have ex-

ceeded their safe operating temperature (≥32˚C/≥270˚F).

Unknown Fault

##

(F##)

The PT controller turned off because the PT controller has sent a fault

code that cannot be determined by the ME-ARC remote.