1 setting up the ags using the me-arc – Magnum Energy ME-ARC Remote User Manual

Page 66

background image

© 2014 Magnum Energy, Inc.

Page 59

Using an AGS Module: Setup

Autostart Condition

Autostop Condition

SETUP Menu

Page

Starts on low battery volt-

age (DC voltage connected

to Terminals #3 and #4)

Stops on higher battery voltage

04A Gen Run VDC

60

Stops at Float charge after a set

time period (using Absorb Done

Time setting)

04A Gen Run VDC

(Set to Float)

60

Stops at Float charge after bat-

tery current requirement is low

(using Absorb Done Amps)

04A Gen Run VDC

(Set to Float)

60

Stops at Float charge using a bat-

tery SOC setting (using Absorb

Done SOC setting)²

04A Gen Run VDC

(Set to Float)

60

Starts daily at a set time

Stops daily at a different set time 04B Gen Run Time

62

Starts on high AC amps to

an inverter load¹

Stops on lower AC amps to an

inverter load¹

04C Gen Run Amps

62

Starts when the battery

SOC² is low

Stops when the battery SOC² is

higher

04D Gen Run SOC

63

Starts when temperature

increases

Stops after a set time period

04E Gen Run Temp

64

Starts when battery SOC²

has been <100% for a set

# of days

Stops when battery SOC² is

100%

04K Gen 100%

SOC Start Days

70

Table 7-2, ME-ARC Autostart/Autostop Matrix

7.1

Setting Up the AGS using the ME-ARC

Press the SETUP button on the ME-ARC remote, and then rotate the SELECT knob to the 04 AGS

Setup display. The menus available from this screen allow the generator to be automatically

started and stopped based on many different conditions. From Table 7-2, determine the specifi c

autostart and autostop conditions with which you want the generator to be automatically con-

trolled, and then use that specifi c menu setting to confi gure the AGS.

Info: For information on using the CTRL, METER, and TECH button menus, refer to

Section 7.2 “Operating/Monitoring the AGS using the ME-ARC”.

Info: The Auto Connect setting must be selected from the CTRL: 01 ACIn Control menu

if a ME-AGS-N is installed and enabled in the system. Otherwise, when the generator

is autostarted it may be prevented from connecting because the criteria to allow the

AC input to connect (02C AC In - Time, 02D AC In - VDC, or 02E AC In - SOC) may not

have been met.
Note: This is true unless you are using an inverter that has two independent AC

inputs—one for grid and the other for generator (i.e., MSH4024RE). On the MSH4024RE

inverter, the AC In control features only work with the GRID IN (AC1) input.

Note¹: Only applicable to MS-PAE, MS-PE and MSH inverters.
Note²: Autostart/stop conditions using SOC require a ME-BMK to be installed.