Using a PT Controller: Operation/Monitoring

Table 10-1, PT Default Settings on ME-ARC

Menu Items

Default Settings

Battery Type

Flooded

Absorb Done

Time = 2.0 Hrs

Max Charge Rate

100%

Max Charge Time

12.0 Hrs

Bulk Start

Daily/SunUp = YES

Volts = 12.0 (12V), 24.0 (24V), 48.0 (48V)

SOC = 80%

PT Aux Relay

Engage Volts = 10.0 (12V), 20.0 (24V), 40.0 (48V)

Engage Delay = 10 Sec

Disengage Volts = 14.0 (12V), 28.0 (24V), 56.0 (48V)

Disengage Delay = 10 Sec

PT Alarm

Alarm ON Volts = 10.0 (12V), 20.0 (24V), 40.0 (48V)

Alarm ON Delay = 10 Sec

Alarm OFF Volts = 14.0 (12V), 28.0 (24V), 56.0 (48V)

Alarm OFF Delay = 10 Sec

PowerSave PT Display

15 Min

First screen – The top line displays the PT fault condition. The bottom line displays the fault his-

tory number (ex. H1), day(s) since this fault occurred, and the time that this fault occurred.
Continue to rotate the SELECT knob to display subsequent screens (bottom lines) for this fault.
Second screen – Displays the PT’s operational status at the time of this fault.
Third screen – Displays the PT’s power status at the time of this fault.
Fourth screen – Displays the PT’s relay status at the time of this fault.
Fifth screen – Displays the battery’s voltage and the battery’s amperage at the time of this fault.
Sixth screen – Displays the voltage of the PV array at the time of this fault.
Seventh screen – Displays the temperature of the PT’s BTS at the time of this fault.
Eighth screen – Displays the temperature of the PT’s FETs at the time of this fault.
Ninth screen – Displays the temperature of the PT’s internal inductors at the time of this fault.
Continue to rotate the SELECT knob to display earlier faults (as applicable).

Figure 10-4, PT Fault History Screens

Time fault

occurred

HiBatt Temp -PT
H1 D– 1 12:23A

HiBatt Temp -PT
H1 No Power Out

HiBatt Temp -PT
H1 Bulk Charging

Fault history

number

Day(s) since

fault occurred

PT Charge Status

at time of fault

Power Status at

time of fault

PT fault

Battery voltage

at time of fault

HiBatt Temp -PT
H1 Engage

HiBatt Temp -PT
H1 11.2V 11.6A

Relay Status at

time of fault

Battery amperage

at time of fault

BTS temp at

time of fault

PV array voltage

at time of fault

FETs temp at

time of fault

Inductor temp

at time of fault

HiBatt Temp -PT
H1 Ind: 83F

HiBatt Temp -PT
H1 FETs: 78F

HiBatt Temp -PT
H1 BTS: 130F

HiBatt Temp -PT
H1 142 VDC