Using an AGS Module: Operation/Monitoring

Info: A solid green STATUS LED means the generator has successfully started and is

providing the generator run sense signal to the AGS controller.

Info: If the generator attempted to start but did not run, continue to wait—the AGS

will attempt to start the generator three more times. If the generator fails to start after

four attempts, the STATUS LED will turn red—indicating a fault.

If a generator fault displays or the AGS’s STATUS LED shows a fault condition (solid red LED in-

dication), refer to Section 7.3.3 for assistance.

7.2

Operating/Monitoring the AGS using the ME-ARC

This section covers the AGS menus under the ME-ARC’s CTRL and METER buttons that determine

the control and operation of the generator. The section also includes menus that are used to help

monitor the AGS and the generator’s starting/running conditions.

7.2.1

Operating the AGS

The AGS uses the CTRL: 01 ACIn Control menu to ensure the incoming AC from the generator is

connected, and the CTRL: 03 Gen Control menu is used to activate the generator either manually

or automatically. Press the CTRL button on the ME-ARC remote to access both menus.
CTRL: 01 ACIn Control
The 01 ACIn Control menu determines the condition in which the inverter/charger connects to an

incoming AC power source. When using a ME-AGS-N, the Auto Connect setting must be selected.

If another ACIn Control setting is enabled, the inverter/charger may be prevented from connect-

ing—when the generator is autostarted—because the criteria to allow the AC input to connect (AC

In based on time, VDC, or SOC) may not have been met.
Note: This is true unless the inverter has two independent AC source inputs—one for grid and

the other for generator—as provided in the MSH4024RE. If you are using a MSH4024RE, then you

can select any AC In selection that is appropriate for your application, because the AC In Control

features only work with the GRID IN (AC1) input.
CTRL: 03 Gen Control
The 03 Gen Control menu is used to control a standby generator that is connected to the system

and using the optional ME-AGS-N controller. Once the AGS-N is installed in the system, the gener-

ator can be manually started and stopped, or set to start and stop automatically from this menu.

Note: Options include: OFF (default setting), ON, and AUTO.

Info: A ME-AGS-N must be installed in order for the 03 Gen Control menu to control

a standby generator. See the ME-AGS-N owner’s manual (PN: 64-0039) for more info.

Info: If a ME-ARC is directly connected to one of a router’s communication ports (P1-

P6), it can be used in a remote location as a remote on/off switch—as well as to assist

in monitoring the system and to control a generator that is connected to an AGS-N.
Info: If a ME-ARC is directly connected to a router, the ARC’s CTRL button function is

defeated. However, the 03 Gen Control selection is in the ARC’s FAVS so the generator

can be controlled via the ARC through the FAVS menu, but not through the CTRL menu.

• OFF

– This selection stops the generator by sending a ‘stop’ command from the ME-AGS-N

controller(can be running from either a manual start or an autostart command from the AGS).

When the OFF setting is selected, the generator will not automatically start.

Info: If DC power is lost to the remote or to the inverter system, this menu resets to

the default OFF selection for safety.

Info: When OFF is selected, the generator turns off immediately—regardless of any

delay settings (i.e., Cooldown).

Info: If the generator is manually started from the generator control panel or a generator

remote panel, selecting OFF on the ME-ARC remote may not shut down the generator.