beautypg.com

4 acld remote status messages, 1 acld remote statuses – Magnum Energy ME-ARC Remote User Manual

Page 104

background image

© 2014 Magnum Energy, Inc.

Page 97

Using an ACLD: Monitoring

Status

Description

Active-Absorb

Current is actively being diverted to the external load to regulate the bat-

tery bank at the Absorb Volts setting*. The ACLD will remain in the Absorb

stage until the SETUP: 03D Absorb Done Time setting has been satisfi ed.

Active-Bulk

If the battery voltage begins rising quickly, the ACLD activates and starts

diverting current in an attempt to keep the voltage from rising above the

Absorb Volts setting*. The ACLD remains in the Bulk stage until the battery

voltage has reached the Absorb Volts setting.

Active-Float

Current is actively being diverted to the external load to regulate the battery

bank at the Float Volts setting*. The ACLD remains in this stage unless the

battery voltage falls to a low voltage, which re-initiates another Bulk stage.

Inactive

The ACLD is on, but inactive (not actively regulating the battery voltage)

because utility power is connected to the Magnum inverter.

No Comm

The ACLD is not communicating with the inverter/remote. This is a normal

status if there is no ACLD connected in the system. If an ACLD is installed,

you may have a bad cable (“ACLD Not Present” displays).

Standby-Absorb The ACLD is not actively diverting current, but the battery voltage has

reached the Absorb Volts setting*. The ACLD remains in the Absorb stage

until the SETUP: 03D Absorb Done Time setting has been satisfi ed, then

goes into the Standby-Float stage.

Standby-Bulk

The ACLD is not actively diverting current, but the battery voltage is below

the Absorb Volts setting*. The ACLD remains in the Bulk stage until the

battery voltage has reached the Absorb Volts setting, then goes into the

Standby-Absorb stage.

Standby-Float

The ACLD is not actively diverting current, but the battery voltage is now

regulating at the lower fl oat voltage level—after being at the higher absorb

voltage level for the required period—to prevent the battery from being

overcharged. While in this status, if the battery voltage falls to a very low

level, another Bulk/Absorb regulation stage will start.

* – These settings are determined by the battery type settings in the Magnum inverter—which

are communicated to the ACLD.

Table 9-1, ACLD Remote Operational Statuses

9.2.4

ACLD Remote Status Messages

A status message may be an operational or fault message. View the ACLD’s current operating

status using the METER: 06A ACLD Status menu. This menu is useful in determining if the ACLD

is working correctly, or for troubleshooting an ACLD installation.
Note: “Fault statuses” indicate that the ACLD is not operating as intended. Refer to Section 9.3.2

“Resolving ACLD Faults using the ME-ARC” to identify and diagnose the problem.

9.2.4.1 ACLD Remote Statuses

Refer to Table 9-1 for a brief description of the possible ACLD operational statuses that may dis-

play (depending on your remote).