beautypg.com

4 fault mode messages – Magnum Energy ME-ARC Remote User Manual

Page 58

background image

© 2014 Magnum Energy, Inc.

Page 51

Operation

• Time

Connect

– AC power is present at the inverter’s AC input, but the time of day needs to

fall within the Connect time and the Disconnect time settings per the SETUP: 02C AC In - Time

menu in order for the inverter/charger to connect to the incoming AC.
• VDC

Connect

– AC power is present at the inverter’s AC input, but the battery voltage needs

to fall below the Connect Volts setting from the SETUP: 02D AC In - VDC menu in order for the

inverter/charger to connect to the incoming AC.
Note: Most faults (inverter, AGS, BMK, and PT controller) also alternate with the inverter/char-

ger status. See Sections 5.3.4, 7.3.3, 8.3.2, and 10.3.2 for more information on identifying and

resolving these faults.

5.3.4

Fault Mode Messages

The FAULT LED comes on and a fault status is displayed when an abnormal condition is detected.

Use the information in this section to identify and correct the issue.

Info: Many of the faults automatically clear once the fault is resolved. Some will require

a manual restart. This requires the ON/OFF INVERTER button on the remote to be

pressed and released. Finally, if the fault will not clear, an inverter reset (Section 6.2)

or power reset (Section 6.3) may be required.

• AC

Backfeed – This fault causes the inverter to shut down because AC voltage from an exter-

nal AC source has been detected on the inverter’s AC output. When the unit shuts down because

of this fault condition, an inverter reset or power reset will be required to resume operation (see

Sections 6.2 & 6.3 to reset the inverter).

Remedy: This fault usually occurs because the AC output wiring is connected to (or

able to be connected to) the incoming AC source. When this fault happens, all system

wiring should be re-checked to ensure the incoming hot and/or neutral wires are not

able to be connected to the AC output.

• AC

Overload – This fault message displays when the AC load on the inverter/charger’s output

has exceeded the inverter’s AC current protection limits. If the overload condition lasts for <10

seconds, the fault automatically clears and the unit restarts and resumes operation. However, if

the overload occurs for more than 10 seconds, the unit shuts down and the fault will require a

manual restart.

Remedy: This fault may occur because the connected AC loads are larger than the

inverter’s output capacity, there is a wiring short on the output, or the output wires are

incorrectly installed. Once the AC loads are reduced or the output wiring is corrected,

the inverter can be restarted after a manual restart.

• Breaker

Tripped

– The AC input breaker on the inverter/charger has opened due to excess

current fl ow through the inverter to the AC loads.

Remedy: After reducing the AC loads, push in the inverter’s AC input circuit breaker to

reset and resume operation.
Info: While in Charger mode, the inverter’s AC input breaker could nuisance trip if the

loads on the inverter’s output exceeds the current rating of the inverter’s input circuit

breaker.

• Dead Batt Charge – This fault indicates that the inverter has been connected to an AC

source (grid or generator), and has determined that the battery bank is either highly discharged

or not connected. The inverter is attempting to close its internal relay and to begin charging, but

has detected less than 9 volts (12-volt models), 18 volts (24-volt models), or 36 volts (48-volt

models) on the battery bank.

Remedy: Check the DC voltage at the inverter’s DC terminals and compare it with the

DC voltage at the battery bank. These two voltages should be very close (<0.5 VDC

difference). If not, check to ensure all connections are tight and the fuse/circuit breaker

between the inverter and battery bank is good.
This fault automatically clears once current fl ows into the battery from the battery

charger—this may take anywhere from a few minutes to a few hours depending on the

condition of your batteries. This fault can also be cleared if the AC input is removed.