Setup

Resetting/Clearing a PIN
You can override a previously entered PIN. When “PIN = 0***” displays, press and hold the SE-

LECT knob until “PIN = 0000” displays (approximately 7 seconds). Enter a new PIN number.
TECH: 06 Ext Control
External Control is a read only menu. Magnum Energy has adopted an open protocol policy which

allows certain functions of the inverter/charger to be controlled externally—such as with a third

party communications device. “Yes” displays if any external device/software is controlling the

remote. This menu is designed to help Magnum Energy technical support personnel determine if

the inverter/charger is operating normally, or being controlled by a third party.
No Ext Control Indicates no third party network device is controlling any inverter/charger

functions or the ME-ARC remote.

Yes – When this display shows a number or a series of numbers (i.e., 04 05 10 20 ## ##

## ##), it indicates that one or more of the allowable functions of the inverter/charger is

currently being controlled externally. The number(s) displayed can be used by Magnum tech-

nicians to determine what function(s) in the inverter/charger is being controlled.

TECH: 07 Show all Menus
This menu enables you to have the ME-ARC remote display all available screens (YES), or to just

display those screens that pertain to the devices and accessories currently active (NO).
TECH: 08 Load Defaults
This menu restores factory defaults to all settings on the inverter/charger and to any defaults

on any accessories that are networked. To restore all defaults, depress the SELECT knob for 5

seconds (once countdown is fi nished the screen displays “DEFAULTS LOADED”). Refer to Table

3-3 for the remote’s inverter/charger default values (see also Table 7-6 and Table 10-1 for the

remote’s AGS and PT default values, respectively).

Info: For information on the factory default settings for any networked accessory, refer

to the owner’s manual for that accessory.

Info: If a PIN has been set and locked, it must be entered before the Load Defaults

menu can be used.

Table 3-3, Inverter/Charger Default Settings on ME-ARC

Menu Items

Default Settings

Menu Items

Default Settings

Max Charge Amps

200 ADC

VAC Dropout

80 VAC (AC1), 70 VAC (AC2)*

(Exports = 150 VAC)

Search Watts

5 Watts

Battery Type

Flooded

LBCO Setting

10 VDC (12v)
20 VDC (24v)
40 VDC (48v)

Absorb Done

Time = 2 Hrs

Amps = 20 ADC

SOC = 100%

AC In - Time

6:00A - 6:00P

Max Charge Rate

100%

AC In - VDC

11.0-14.1 VDC (12v)
22.0-28.2 VDC (24v)
44.0-56.4 VDC (48v)

Max Charge Time

12.0 Hrs

AC In - SOC

80%, 100% SOC

Final Charge Stage

Multi

Power Up Always

OFF

ReBulk Volts

12.0 VDC

AC Input Amps

30A (AC1), 20A (AC2)*

EQ Reminder Days

OFF

* AC2 settings available on MSH4024RE models only.