Using an AGS Module: Operation/Monitoring

7.2.6.2 AGS Remote Start Statuses

The following “Start” statuses identify the condition that autostarted the generator. If you deter-

mine that the autostart condition occurred sooner than expected (or didn’t want this autostart

condition), refer to the Section 7.1 “Setting Up the AGS using the ME-ARC” to change (or defeat)

the autostart setting.

Status

Description

Start Amp

Generator has autostarted based on the SETUP: 04C Gen Run Amps set-

ting.

Start Exercise

Generator has autostarted based on the SETUP: 04H Gen Exercise setting.

Start SOC

Generator has autostarted based on the SETUP: 04D Gen Run SOC setting.

Start Temp

Generator has autostarted based on the SETUP: 04E Gen Run Temp setting.

Start Test

The AGS is in Test mode. Test mode may be started from the TEST button

located on the AGS.

Start Time

Generator has autostarted based on the SETUP: 04B Gen Run Time setting.

Start Topoff

Generator has autostarted based on the SETUP: 04G Quiet Time Topoff

setting.

Start VDC

Generator has autostarted based on the SETUP: 04A Gen Run VDC setting.

Start 100% SOC Generator has autostarted based on the SETUP: 04K Gen 100% SOC Start

Days setting.

Table 7-4, AGS Remote Start Statuses

7.2.6.3 AGS Remote Fault Statuses

The following “Fault” statuses indicate that the generator wasn’t able to start based on an ex-

pected autostart condition. Refer to Section 7.3.3 “Resolving AGS Faults using the ME-ARC” for

help in diagnosing the problem.

Table 7-5, AGS Remote Fault Statuses

Status

Description

Fault Amp

Generator failed to autostart in Start Amps mode.

Fault Exercise

Generator failed to autostart in Start Exercise mode.

Fault Gen Run

Generator successfully started and ran for more than two minutes, but un-

expectedly stopped before the AGS could automatically stop the generator.

Fault MaxRn

Generator turned off because the SETUP: 04F Max Gen Run Time setting

had been met. This fault can occur when: 1) an autostop parameter has

been met, but it did not stop the generator, or, 2) the autostop condition

exceeded the Max Gen Run Time setting.

Fault SOC

Generator failed to autostart in Start SOC mode.

Fault Temp

Generator failed to autostart in Start Temp mode.

Fault Test

Generator failed to start in Test mode.

Fault Time

Generator failed to autostart in Start Time mode.

Fault Topoff

Generator failed to autostart in Start Topoff mode.

Fault VDC

Generator failed to autostart in Start VDC mode.

Fault 100% SOC Generator failed to autostart in 100% SOC Start Days mode.