13  Directory of the Parameters in Installer Mode and Expert Mode

SMA Solar Technology AG

94

SI30M-44M-60H-80H-BE-en-30

Operating Manual

132# Grid State

133# Gen State

No.

Name

Description

Value (plain

text no.)

Explanation

132.01 GdStt

Status of the

management for the

operation on the utility

grid (expert mode)

Off (1)

Grid operation is disabled.

✓ ✓

Init (2)

Utility grid has been detected.

Detect (3)

Grid monitoring started.

Wait (4)

Waiting until the stand-alone grid is

synchronized with the utility grid.

RunVExt (5)

The stand-alone grid is synchronized

with and connected to the utility grid.

Feed (6)

Grid feed-in into the utility grid is

possible.

Silent (7)

The Sunny Island is in energy saving

mode.

SiStr (8)

The Sunny Island is switching to energy

saving mode.

SiStp (9)

The Sunny Island is leaving energy

saving mode.

Error (10)

An error occurred when connecting.

Reinit (11)

Utility grid has been re-detected.

132.02 GdRmgTm Remaining time of grid

monitoring in hh:mm:ss

✓ ✓

No.

Name

Description

Value (plain

text no.)

Explanation

133.01 GnDmdSrc Source for generator

request

None (1)

No request

✖ ✓

Bat (2)

State-of-charge-dependent request

Lod (3)

Load-dependent request

Tim (4)

Time-controlled request

Run1h (5)

Requested for 1 hour

Start (6)

Manually started

ExtSrcReq (7)

External generator request