SMA SI 3.0-11 User Manual
Page 94
13 Directory of the Parameters in Installer Mode and Expert Mode
SMA Solar Technology AG
94
SI30M-44M-60H-80H-BE-en-30
Operating Manual
132# Grid State
133# Gen State
No.
Name
Description
Value (plain
text no.)
Explanation
132.01 GdStt
Status of the
management for the
operation on the utility
grid (expert mode)
Off (1)
Grid operation is disabled.
✓ ✓
Init (2)
Utility grid has been detected.
Detect (3)
Grid monitoring started.
Wait (4)
Waiting until the stand-alone grid is
synchronized with the utility grid.
RunVExt (5)
The stand-alone grid is synchronized
with and connected to the utility grid.
Feed (6)
Grid feed-in into the utility grid is
possible.
Silent (7)
The Sunny Island is in energy saving
mode.
SiStr (8)
The Sunny Island is switching to energy
saving mode.
SiStp (9)
The Sunny Island is leaving energy
saving mode.
Error (10)
An error occurred when connecting.
Reinit (11)
Utility grid has been re-detected.
132.02 GdRmgTm Remaining time of grid
monitoring in hh:mm:ss
‒
‒
✓ ✓
No.
Name
Description
Value (plain
text no.)
Explanation
133.01 GnDmdSrc Source for generator
request
None (1)
No request
✖ ✓
Bat (2)
State-of-charge-dependent request
Lod (3)
Load-dependent request
Tim (4)
Time-controlled request
Run1h (5)
Requested for 1 hour
Start (6)
Manually started
ExtSrcReq (7)
External generator request