3 saving the event history and error history, 4 displaying the sd memory card status message, 5 removing the sd memory card – SMA SI 3.0-11 User Manual
Page 34: 6 displaying the sd memory card content

6 Data Storage and Firmware Update
SMA Solar Technology AG
34
SI30M-44M-60H-80H-BE-en-30
Operating Manual
6.3 Saving the Event History and Error History
Requirement:
☐ The SD memory card must be inserted.
Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. To save the event history, select the parameter 550.03 CardFunc and set to StoEvtHis.
3. To save the error history, select the parameter 550.03 CardFunc and set to StoFailHis.
4. To save the error history and the event history, select the parameter 550.03 CardFunc and set to StoHis.
6.4 Displaying the SD Memory Card Status Message
The Sunny Remote Control determines the SD memory card status (see Section 13.3.1 "Inverter (310#)", page 123).
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Select the parameter 312.11 CardStt and read off the value.
6.5 Removing the SD Memory Card
If the SD memory card is removed without preparation, the removal will cause data loss. Data loss affects the log data
of the last 15 minutes at most.
Procedure
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Select the parameter 550.03 CardFunc and set to ForcedWrite. Unsaved data will now be saved to the
SD memory card.
3. Remove the SD memory card.
6.6 Displaying the SD Memory Card Content
Figure 15: Content of an SD memory card (example)
The files saved to the SD memory card depend on the configuration and on the system.
Explanation of the folders:
Folder name
Explanation
BATSTAT
Folder containing battery statistics for each month
The files are stored by year and month in sub-folders.
HISTORY
Folder containing event and error histories
LOGGING
Folder containing the data logging, event and error histories for each day
The files are stored by year and month in sub-folders.
SIPAR
Folder containing the parameter lists